(60KVA - 120KVA) 3P OFF GRID HYBRID INVERTER
Our USP:
Bi Directional | Seamless switching to and from grid (both import and export) and batterysupply, high-efficiency MPPT technology |
GRID-INTERACTIVE | Blends solar and grid- power for optimisation |
IEC CERTIFIED | IEC certifications available |
PURE SINE WAVETECHNOLOGY | Recommended for longer life of Industrial/Commercial equipment |
INTELLIGENT BATTERYCHARGING | 3-Stage charging (Float, Bulk & Absorption) for more battery life (for LeadAcid batteries). Communication-based charging for Lithium chemistriesavailable |
COMPATIBLE CHARGER Supports | Supports wide range of batteries-Flooded Lead Acid Tubular/GEL/VRLA. Onrequest product for Li+ |
PRONTO RENEWABLES ENERGY PVT LTD | ||||||
PRONTO 3P SOLAR OFF GRID/HYBRID INVERTER - SPECIFICATIONS | ||||||
INVERTER RATING (KVA) | 60KVA | 80KVA | 100KVA | 100KVA | 120KVA | |
BATTERY VOLTAGE | 360V | 480V | 360V | 480V | 360 | |
SOLAR CHARGE CONTROLLER | TECHNOLOGY-MPPT/VOC RANGE 415-900V | TECHNOLOGY-MPPT/VOC RANGE 552-900V | TECHNOLOGY-MPPT/VOC RANGE 415-900V | TECHNOLOGY-MPPT/VOC RANGE 552-900V | TECHNOLOGY-MPPT/VOC RANGE 415-900V | |
A | SOLAR CHARGE CONTROLLER | |||||
1 | Charger Type & Topology | Buck Type MPPT | ||||
2 | PV Total Nominal Capacity (KW) | 60 KW | 80KW | 100KW | 100KW | 120KW |
3 | Per Channel PV Capacity (w)(Nominal Peak) | 60KW/66KW | 80KW/88KW | 100KW/110KW | 100KW/110KW | 120KW/132KW |
4 | PV Minimum Voltage (Volts) | 415 | 552 | 415 | 552 | 415 |
5 | Max. I/P Amps per channel (Amps) | 55 | 45 | 61 | 57 | 75 |
6 | Max. Battery Amps during PV charging | 125 | 125 | 210 | 158 | 250 |
7 | Battery type Supported | VRLA / LMLA / Li-ion/ LiFePo4 (User Settable) | ||||
8 | Min. Battery AH (Suggested) | 300 | 300 | 300 | 300 | 300 |
9 | Peak charging Efficiency MPPT (%) | >93% | >93% | >93% | >93% | >93% |
A.1 | MPPT Charger Controller | |||||
1 | No. Of MPPT Channels | 2 | 3 | 3 | 3 | 3 |
2 | Max.Open Circuit PV Volts (Voc) MPPT | 900 | 900 | 900 | 900 | 900 |
3 | MPPT Voltage Range (Volts) | 415-900 | 552-900 | 415-900 | 552-900 | 415-900 |
4 | Max. SCC O/P (Amps) | 125 | 125 | 210 | 158 | 250 |
B | SOLAR INVERTER | |||||
1 | No. of Phases/Connection Type | 3Phase/4 wire | ||||
2 | Nominal KW Capacity (KW) (Tortal Per Phase)(*4) | 48.0/16.0 | 64.0/21.3 | 80.0/26.6 | 80.0/26.6 | 96.0/32.0 |
3 | Nominal Battery Voltage | 360 | 480 | 360 | 480 | 480 |
4 | Nominal Output Voltage/ Frequency (Volts/Hz) | 415/50 | 415/50 | 415/50 | 415/50 | 415/50 |
5 | Output Amp per Phase (*4) | 69.6 | 92.6 | 115.6 | 115.6 | 139.1 |
6 | Voltage Regulation (in Standalone Mode) | ± 2% | ± 2% | ± 2% | ± 2% | ± 2% |
7 | Freq. Regulation (in Standalone Mode) | ± 0.5 Hz | ± 0.5 Hz | ± 0.5 Hz | ± 0.5 Hz | ± 0.5 Hz |
8 | THD | <3% | <3% | <3% | <3% | <3% |
9 | Load Power Factor | 0.8 lag to unity | ||||
10 | Efficiency (%): Peak/ 100% Load/25% Load | >92/ >90/ >85 | >92/ >90/ >85 | >92/ >90/ >85 | >92/ >90/ >85 | >92/ >90/ >85 |
11 | Over Loads : | 100-110% - 60 sec | ||||
12 | 110-125% - 30 sec | |||||
13 | 125-150% - 5 sec | |||||
14 | Max Alowed Phase Imbalnce (%) | 100% | 100% | 100% | 100% | 100% |
15 | Auto Bypass Feature | Provided | Provided | Provided | Provided | Provided |
16 | Parallel Operation with grid/DG | Provided | Provided | Provided | Provided | Provided |
17 | Power Export to Grid Facility Enable/Disable) | Enable/Disable (User Settable) | ||||
18 | Anti Islanding from Grid | Provided | Provided | Provided | Provided | Provided |
C | GRID CHARGER | |||||
1 | Grid Voltage Range (Voltage Sync. Range) | 160V-280V (Phase to Neutral) | ||||
2 | Grid Frequency Range (Freq. Sync. Range) | 50 Hz ± 5% | ||||
3 | Max. Grid Import Power (KW) | 48KW | 64KW | 80KW | 80KW | 96KW |
4 | Peak charging Efficiency (%) | >87 | >87 | >87 | >87 | >87 |
5 | Max Battery Amps During Grid Charging (Amps) | 95 | 95 | 157.8 | 118 | 189 |