40KVA / 240V 3P HYBRID INV

Our USP:

Bi DirectionalSeamless switching to and from grid (both import and export) and batterysupply, high-efficiency MPPT technology
GRID-INTERACTIVEBlends solar and grid- power for optimisation
IEC CERTIFIEDIEC certifications available
PURE SINE WAVETECHNOLOGYRecommended for longer life of Industrial/Commercial equipment
INTELLIGENT BATTERYCHARGING3-Stage charging (Float, Bulk & Absorption) for more battery life (for LeadAcid batteries). Communication-based charging for Lithium chemistriesavailable
COMPATIBLE CHARGER SupportsSupports wide range of batteries-Flooded Lead Acid Tubular/GEL/VRLA. Onrequest product for Li+

PRONTO RENEWABLES ENERGY PVT LTD

PRONTO 40KVA SOLAR INVERTER AGNI SERIES - SPECIFICATIONS
INVERTER RATING (KVA)40KVA
BATTERY VOLTAGE240V
SOLAR CHARGE CONTROLLERTECHNOLOGY-MPPT/VOC RANGE 275-7000V/MAX. 125Amp
ASOLAR CHARGE CONTROLLER 
1Charger Type & TopologyBuck Type MPPT
2PV Total Nominal Capacity (KW)40 KW
3Per Channel PV Capacity (w)(Nominal Peak)40KW/44KW
 PV Minimum Voltage (Volts)275
4Max. Battery Charging Amps during PV Charging (Amps)125
5Battery type SupportedVRLA / LMLA / Li-ion/ LiFePo4 (User Settable)
6Min. Battery AH (Suggested)300
7Peak charging Efficiency MPPT (%)>93%
A.1MPPT Charger Controller 
1No. Of MPPT Channels2
2Max.Open Circuit PV Volts (Voc) MPPT700
3MPPT Voltage Range (Volts)275-700
 Max.I/P Amps per channel (Amps)50
4Max. SCC O/P (Amps)125
BSOLAR INVERTER 
1No. of Phases/Connection Type3Phase/4 wires
 Nominal Battery Voltage (Volts)240
2Nominal Output Voltage/Frequency (Volts/Hz)415/50hz
3Nominal KW Capacity (KW) (Total Per Phase) (*4)32/10.7
4Output Amps Per Phase (*4)46.4
5Voltage Regulation (in Standalone Mode)±2%
6Freq. Regulation (in Standalone Mode)±0.5 Hz
7Inverter Load Capacity (W) (BULB LOAD)1.2KW
9THD<3%
10Load Power Factor0.8 lag to unity
11Efficiency (%): Peak/100% Load/25% Load>92/ >90/ >85
12Over Loads :100-110% - 60 sec
13110-125% - 30 sec
14125-150% - 5 sec
15Max Alowed Phase Imbalnce (%)100%
16Auto Bypass FeatureProvided
17Parallel Operation with grid/DGProvided
18Power Export to Grid Facility Enable/Disable)Enable/Disable (User Settable)
19Anti Islanding from GridProvided
CGRID CHARGER
1Grid Voltage Range (Voltage Sync. Range)160V-280V (Phase to Neutral)
2Grid Frequency Range (Freq. Sync. Range)50 Hz ± 5%
3Max. Grid Import Power (KW)32 (KW)
4Max. Battery Amps During Grid Charging (Amps)95
5Peak charging Efficiency (%)>87